LEYPOWER ready-to-use diesel generating sets meet with the latest CPCB norms in India and built to comfortably meeting international norms. These sets are powered by the compact 4, 6, 8 and 12 cylinder series of diesel engines. Aesthetically designed, these DG sets are silent, environment-friendly require minimum maintenance and are low on operating costs.

Leypower diesel generating sets are manufactured in the state-of-the-art plants located across 6 units in the country using the latest machinery and skill sets to roll out well engineered DG sets.

The present range extends from 10-2250 kVA with generating sets manufactured to operate under arduous conditions.

SPECIFICATION
parameters description
Power Rating (KVA) 40
Electric Power (KWe) 32
Rated Current (A) 55.6
No of Phases/Volts* 3/415
Oveall Dimensions (L X W X H, mm x mm x mm) 2500 x 1100 x 1350
Fuel Tank Capacity (Litres) 50 / 60
Battery Capacity (AH) 99
System Voltage (VDC) 12
Weight (Kg) 1086
ENGINE SPECIFICATION
Parameters Description
Engine Model WO4DMK1
Engine Rated HP 48.7
Aspiration Natural
No of Cylinders 4
Bore & Stroke (mm x mm) 104 x 118
Displacement (Litres) 4.009
Compression Ratio 17.9:1
Lub oil Sumb Capacity (Litres) 7.5
Coolant Capacity (Litres) 15.0
Governing Class A1
ALTERNATOR SPECIFICATION
Parameters Description
Model P 14J1
Type 4 pole
Exciter type Brushless
Voltage regulator AVR-AS480
Insulation Class H
Temperature rise (°C) 125
Bearing ±Single
Voltage regulation ±0.5%
Rated Voltage (V) 415
SPECIFICATION FOR STANDARD MANUAL PANEL
Parameters Description
SWITCH GEAR 3pole MCB / MCCB
Analogue Gauge
  • Water Temperature

  • Lube Oil Pressure

  • Engine RPM

  • Battery Charging Ammeter

  • Running-Hour Counter

Digital Multifunction meter Voltage/Ampere/Frequency
Fault Indication (LED Type on Engine safety Unit)
  • Low Oil pressure

  • Battery Charger Failure

  • High Engine Temperature

  • Low fuel level

Current Transformers of suitable rating
Indications (LED):
  • DG ON

  • Load on DG

Control Key switch for Start/Stop
SPECIFICATION FOR STANDARD AMF PANEL
Parameters Description
SWITCH GEAR
  • 4 Pole Contactor for DG

  • 4 Pole Contactor for MAINS

  • MCB / MCCB for short circuit protection

Features
  • Monitoring of engine protection

  • Alphanumeric LCD Display

  • Supervision of Mains and DG voltage

  • Mains and DG contactor interlock

  • Provision for Remote start / stop

  • Parameter setting by front panel key board

  • Auto / Manual mode operation

  • Programmable parameters / timers

Multifunction meter
  • Voltage

  • Ampere

  • Frequency

Analogue meter
  • Oil pressure

  • Water Temperature

  • Engine RPM

Indication Lamps
  • Mains On

  • DG On

  • Load on Mains

  • Load on DG

POWER RATING
Parameters Description
Reference condition (Dec C Ambient Temp) 27
Atmospheric Condition (KPA-750mm of Hg) 100
Humidity 60% - As per IS10002, ISO 3046