Product

ASHOK LEYLAND AL 6H Series - LP100 (100KVA) Generator

 

Description

LEYPOWER Power Solutions is the fastest growing genset provider in India. With state-of-the-art technology in engine, alternator and controllers, LEYPOWER provides a fully integrated power system at par with global standards at a very competitive overall cost of ownership.

LEYPOWER ready-to-use diesel generating sets meet with the latest CPCB norms in India and built to comfortably meeting international norms. These sets are powered by the compact 4, 6, 8 and 12 cylinder series of diesel engines. Aesthetically designed, these DG sets are silent, environment-friendly require minimum maintenance and are low on operating costs.

Leypower diesel generating sets are manufactured in the state-of-the-art plants located across 6 units in the country using the latest machinery and skill sets to roll out well engineered DG sets.

The present range extends from 10-2250 kVA with generating sets manufactured to operate under arduous conditions.

SPECIFICATION
parameters description
Power Rating (KVA) 100
Electric Power (KWe) 80
Rated Current (A) 139
No of Phases/Volts* 3/415
Oveall Dimensions (L X W X H, mm x mm x mm) 3300 x 1250 x 1530
Fuel Tank Capacity (Litres) 200 / 60
Battery Capacity (AH) 120
System Voltage (VDC) 12
Weight (Kg) 1874
ENGINE SPECIFICATION
Parameters Description
Engine Model AL6DTIG1
Engine Max HP 134.0
Engine Rated HP 122.0
Aspiration TA
No of Cylinders 6
Bore & Stroke (mm x mm) 104*113
Displacement (Litres) 5.7
Compression Ratio 17.5:1
Lub oil Sumb Capacity (Litres) 12.0
Lub oil Consumption <0.3%
Coolant Capacity (Litres) 16.0
Governing Class Electronic A1
ALTERNATOR SPECIFICATION
Parameters Description
Model UC 274C
Type 4 pole
Exciter type Brushless
Voltage regulator AVR-SX 460
Insulation Class H
Temperature rise (°C) 125
Bearing ±Single
Voltage regulation ±0.5%
Rated Voltage (V) 230
SPECIFICATION FOR STANDARD MANUAL PANEL
Parameters Description
SWITCH GEAR 3pole MCB / MCCB
Analogue Gauge
  • Water Temperature

  • Lube Oil Pressure

  • Engine RPM

  • Battery Charging Ammeter

  • Running-Hour Counter

Digital Multifunction meter Voltage/Ampere/Frequency
Fault Indication (LED Type on Engine safety Unit)
  • Low Oil pressure

  • Battery Charger Failure

  • High Engine Temperature

  • Low fuel level

Current Transformers of suitable rating
Indications (LED):
  • DG ON

  • Load on DG

Control Key switch for Start/Stop
SPECIFICATION FOR STANDARD AMF PANEL
Parameters Description
SWITCH GEAR
  • 4 Pole Contactor for DG

  • 4 Pole Contactor for MAINS

  • MCCB for short circuit protection

Features
  • Monitoring of engine protection

  • Supervision of Mains and DG voltage

  • Mains and DG contactor interlock

  • Provision for Remote start / stop

  • Parameter setting by front panel key board

  • Auto / Manual mode operation

  • Programmable parameters / timers

Multifunction meter
  • Voltage

  • Ampere

  • Frequency

Analogue meter
  • Oil pressure

  • Water Temperature

  • Engine RPM

Indication Lamps
  • Mains On

  • DG On

  • Load on Mains

  • Load on DG

POWER RATING
Parameters Description
Reference condition (Dec C Ambient Temp) 27
Atmospheric Condition (KPA -750mm of Hg) 100
Humidity 60% - As per IS10002, ISO 3046

© 2016,Universal Electricals. All rights reserved. || Develop By :: Core Objects